5.3 · Calculate refrigerator COP from enthalpy differences
Learn to calculate refrigerator cop from enthalpy differences through clear examples and targeted practice.
University of Alberta MEC E 340: Applied Thermodynamics
Refrigeration and Heat Pumps
A focused method for a simple vapour-compression refrigeration cycle
Start with a steady-flow control volume around a simple vapour-compression refrigerator. The working fluid is the refrigerant, which circulates through four numbered states: state 1 is the evaporator outlet and compressor inlet; state 2 is the compressor outlet; state 3 is the condenser outlet; and state 4 is the expansion-valve outlet. Refrigerant flows in the order 1 to 2 to 3 to 4 to 1. Unless a problem states otherwise, the calculations here use steady operation and negligible kinetic and potential energy changes. The compressor and valve models are stated where used. Numerical enthalpies are supplied as problem data, not taken from an unstated property source.
What you will learn
Identify the four refrigerant states and energy transfers used in a refrigerator COP calculation.
Use supplied enthalpies and stated component models to find cooling effect and compressor work input per unit mass.
Calculate refrigerator COP and check its signs, units, and physical meaning.
1. Connect component energy balances to COP
A refrigerator removes heat from a cooled space and requires work input. Its coefficient of performance, or COP, compares useful cooling with compressor work input. It is a dimensionless performance ratio, not a thermal efficiency. A refrigerator COP can be greater than one because the refrigerator moves heat from the cooled space to its surroundings; work input is not the only energy involved.
For a steady-flow component with one inlet and one outlet, the first-law balance relates heat transfer, work, and the change in specific enthalpy. In this lesson, changes in kinetic and potential energy are negligible. In the evaporator, heat enters the refrigerant as it flows from state 4 to state 1. Cooling per unit mass is therefore the outlet enthalpy minus the inlet enthalpy.
For an adiabatic compressor with negligible kinetic and potential energy changes, work is supplied to the refrigerant as it flows from state 1 to state 2. Compressor work input per unit mass is the enthalpy rise through the compressor. If a problem specifies compressor heat transfer or another energy effect, use the corresponding full energy balance rather than this simplified relation.
Use positive values for cooling and compressor work input. Divide the evaporator enthalpy rise by the compressor enthalpy rise. Both differences are specific energy transfers, so their units cancel. A mass flow rate is not needed for COP when both terms are calculated on the same per-unit-mass basis.
The refrigerator COP is cooling per unit mass divided by compressor work input per unit mass. The subscripts distinguish heat removed from the cooled space from work supplied to the compressor.
COPR=h2−h1h1−h4
Evaporator cooling per unit mass is the enthalpy rise from state 4 to state 1.
For an adiabatic compressor with negligible kinetic and potential energy changes, work input per unit mass is the enthalpy rise from state 1 to state 2.
COP is dimensionless because its numerator and denominator have matching units.
2. Assign states and apply the valve model
Follow refrigerant flow around the cycle: compressor, condenser, expansion valve, and evaporator. State 1 is both the compressor inlet and evaporator outlet. State 4 is both the valve outlet and evaporator inlet. Keep these labels fixed when recording property data and writing balances.
An expansion valve is often represented as isenthalpic. Under that stated model, enthalpy at the valve outlet equals enthalpy at its inlet. Use this relation only when the problem specifies an isenthalpic valve or otherwise supplies a justified model. A pressure drop alone does not determine the outlet enthalpy.
The condenser rejects heat as refrigerant flows from state 2 to state 3. That heat rejection is not the cooling effect used in refrigerator COP. Cooling is the heat absorbed from the cooled space in the evaporator. The denominator is compressor work input, not condenser heat rejection.
Write each supplied enthalpy beside its state number and retain its units. If the valve is specified as isenthalpic and the condenser outlet enthalpy is known, use it to obtain the valve outlet enthalpy. Then calculate the evaporator and compressor enthalpy differences. This keeps the state connections and subtraction directions clear.
h4=h3
Use state numbers consistently with refrigerant flow direction.
For a specified isenthalpic valve, the inlet and outlet enthalpies are equal.
Condenser heat rejection is not the cooling quantity used in refrigerator COP.
3. Calculate and check performance
Calculate cooling and compressor work input separately before dividing. If enthalpies are given in kilojoules per kilogram, both differences are in kilojoules per kilogram. These units cancel in the COP ratio. A supplied mass flow rate can convert specific energy transfers to rates, but it is not required for COP when both terms use the same mass basis.
Check signs against the intended operating direction. Cooling is positive when refrigerant enthalpy rises from state 4 to state 1. Under the stated compressor model, work input is positive when enthalpy rises from state 1 to state 2. If a difference has an unexpected sign, check the state labels, flow direction, and subtraction order before interpreting the result.
A COP greater than one is physically plausible. It means that more heat is removed from the cooled space than the work supplied to the compressor, while the refrigerator also rejects heat at the condenser. COP is not a percentage and should not be described as the fraction of work converted into cooling.
A schematic cycle plot helps show state order and component processes, but it does not provide exact property coordinates or phase boundaries. For numerical work, use enthalpy data and assumptions supplied in the problem, not values guessed from a sketch.
Find cooling and compressor work input separately, then divide.
Check state labels, signs, and matching units.
Treat schematic cycle plots as illustrations, not sources of numerical property data.
Worked example
Direct COP calculation
A refrigerator follows the four-state cycle defined above. Supplied enthalpies are h1=242kJ/kg, h2=278kJ/kg, and h3=92kJ/kg. The valve is modelled as isenthalpic and the compressor as adiabatic. Find the cooling effect, compressor work input, and refrigerator COP per unit mass.
Four-state vapour-compression cycle
The refrigerant cycle is schematic and not to scale on a pressure–specific-volume plane.
Find the valve outlet enthalpy
The stated isenthalpic valve model means enthalpy is unchanged from state 3 to state 4.
h4=h3=92kJ/kg
Calculate cooling and compressor work
Cooling is the enthalpy rise from state 4 to state 1. Compressor work input is the enthalpy rise from state 1 to state 2. q_L=h_1-h_4=242-92=150\ kJ/kg, w_{in}=h_2-h_1=278-242=36\ kJ/kg
Form the COP
Divide the cooling effect by compressor work input. Their specific-energy units cancel.
COPR=36150=4.17
Answer: The cooling effect is 150kJ/kg, compressor work input is 36kJ/kg, and refrigerator COP is 4.17.
Check: Both enthalpy differences are positive and have the same units. The result means about 4.17kJ of heat is removed from the cooled space per kilojoule of compressor work input.
Worked example
Calculate COP when valve enthalpy is needed
A refrigerator has supplied enthalpies h1=410kJ/kg, h2=446kJ/kg, and h3=180kJ/kg. The expansion valve is isenthalpic and the compressor is adiabatic. Calculate h4, the cooling effect, compressor work input, and COP.
Four-state refrigerator cycle
The refrigerant cycle is schematic and not to scale on a pressure–specific-volume plane.
Determine the evaporator inlet enthalpy
The stated isenthalpic valve model connects states 3 and 4 without an enthalpy change.
h4=h3=180kJ/kg
Apply the component enthalpy differences
Use the rise from state 4 to state 1 for cooling and the rise from state 1 to state 2 for compressor work input. q_L=410-180=230\ kJ/kg, w_{in}=446-410=36\ kJ/kg
Calculate COP
The specific energy transfers have matching units, so their ratio has no units.
COPR=36230=6.39
Answer:h4=180kJ/kg, cooling effect is 230kJ/kg, compressor work input is 36kJ/kg, and refrigerator COP is 6.39.
Check: Cooling and compressor work input are positive. COP is dimensionless, not a percentage.
Worked example
Infer enthalpies from specified cooling
A refrigerator has h1=205kJ/kg and h2=239kJ/kg. Its cooling effect is 125kJ/kg. The expansion valve is isenthalpic and the compressor is adiabatic. Determine h4, infer h3, and calculate COP.
Four-state refrigerator cycle
The refrigerant cycle is schematic and not to scale on a pressure–specific-volume plane.
Find the evaporator inlet enthalpy
Cooling is the enthalpy rise from state 4 to state 1. Rearranging this relation gives the enthalpy at state 4.
h4=h1−qL=205−125=80kJ/kg
Infer the condenser outlet enthalpy
The stated isenthalpic valve model means states 3 and 4 have equal enthalpies.
h3=h4=80kJ/kg
Calculate compressor work and COP
Find work input from the compressor enthalpy rise, then divide the given cooling effect by that work input. w_{in}=239-205=34\ kJ/kg, COP_R=34125=3.68
Answer:h4=80kJ/kg, h3=80kJ/kg, compressor work input is 34kJ/kg, and refrigerator COP is 3.68.
Check: The enthalpy at state 4 is below h1, so evaporator cooling is positive. Compressor work input is also positive, and the enthalpy differences use kilojoules per kilogram.
Common mistakes and how to avoid them
Using h4−h1 for cooling.
Correction: The refrigerant absorbs heat as it flows from state 4 to state 1, so use h1−h4. Check that cooling is positive.
Using h1−h2 for compressor work input.
Correction: Under the stated adiabatic-compressor model, work input is positive when enthalpy rises through the compressor. Use h2−h1.
Assuming h3=h4 without checking the valve model.
Correction: That equality applies only when the expansion valve is specified as isenthalpic.
Giving COP units or reporting it as a percentage.
Correction: The numerator and denominator are both energy per unit mass, so the units cancel. COP is dimensionless, not a percentage.
Lesson summary
For this simple cycle, state 1 is the compressor inlet, state 2 its outlet, state 3 the condenser outlet, and state 4 the valve outlet.
With the stated steady-flow assumptions, cooling per unit mass is h1−h4 and compressor work input per unit mass is h2−h1.
For an isenthalpic expansion valve, use h4=h3 only when that model is specified.
Divide cooling by compressor work input to calculate refrigerator COP, then check signs, units, and state assignments.
Check your understanding
Question 1
For a cycle with h1=260kJ/kg, h2=300kJ/kg, and h4=110kJ/kg, what is refrigerator COP?
3.75
4.75
0.267
1.50
Show answer and explanation
3.75
Cooling is 260−110=150kJ/kg and compressor work input is 300−260=40kJ/kg. Therefore, COP is 150/40=3.75.
Question 2
A problem states that the expansion valve is isenthalpic and gives h3=95kJ/kg. What value should be used for h4?
h3+h2
h3−h1
95kJ/kg
It cannot be found without the mass flow rate
Show answer and explanation
95kJ/kg
For the stated isenthalpic valve model, h4=h3, so h4=95kJ/kg. Mass flow rate is not needed for this state relation.
Key terms
Refrigerator COP
Heat absorbed from the cooled space divided by compressor work input, evaluated on the same basis.
Enthalpy
A thermodynamic property used in steady-flow energy balances; here it is given as energy per unit refrigerant mass.
Isenthalpic throttling
The specified expansion-valve model in which enthalpy is unchanged between valve inlet and outlet.
Published by DoAssignment. This reviewed lesson follows University of Alberta MEC E 340: Applied Thermodynamics, study topic 5.3. It is a study resource, not an official curriculum publication.
Before publication, content is checked for structure, mathematical or chemical notation, calculations, course boundaries, and readability. Errors can still occur, so corrections are welcomed.